Alarms

An alarm is a condition on a tag. It is digital (a Bool tag or a word bit) or analog (a comparison with a limit).

Active alarms

Parameter Meaning
Name Unique; used to acknowledge the alarm and find it in the journal
Tag, bit The source; the bit is for status words
Condition On, off, above, below, equal, not equal
Limit A number or another tag; the tag takes priority
Deadband “Above 8.5” with a 0.1 deadband clears only below 8.4
On delay Filters out short spikes
Off delay The condition must stay absent for this long
Priority Critical, high, medium, low
Acknowledgement Without it, an alarm disappears as soon as it clears
Message {value}, {limit} and {unit} substitutions
Area Plant area for filtering

Operators can acknowledge one alarm or all of them, which requires the Acknowledge permission. Shelving requires a separate permission.

The journal is stored in %ProgramData%\Scadora\alarms.db and kept for 365 days by default. Set Scada:AlarmJournal:RetentionDays to change it.

Alarm journal